Reference only — this item is no longer available.
This product has been discontinued and cannot be ordered. We keep the page online so the specifications and documentation stay available to anyone still running the equipment. Current replacements are listed further down.
Discontinued
Product details (archived)
The information below is retained for reference only. This item is discontinued and cannot be ordered.
Description | Specifications/Features | FAQ |
Related Products | Uses | Blog | Manual
Description
Smoke Check™ smoke detector tester in a ½ ounce promotional size can perform approximately 12 tests and fits in a shirt pocket.
To learn more about Smoke Check™ smoke detector tester please visit
2.5 Ounce Smoke Check™.
Please Note: Pressing the "test button" on a smoke detector tests battery strength only. The test button cannot be used to verify the smoke
detector's ability to activate its alarm in the presence of smoke caused by a fire. Smoke Check™ Smoke Detector Tester was designed specifically
to verify the smoke detector's proper functioning.
TOP
Specifications & Features
- Over 12 Smoke Detector Tests Possible Per Can
- Contents Net Weight - 0.5 oz
- Contains No Hydrofluorocarbons (HFCs)
- 100% Ozone Safe
- Smoke Check™ is UL Listed (per NFPA 72 par. 8-2.4.1)
- Due to Federal Law, Smoke Detector Tester Smoke in a Can cannot be
shipped via the US Postal Service or by any Air Method.
- Made in USA
- Smoke Detector Tester (Model SAT-1) may only be shipped within the continental United States.
- Manufacturer Provides 100% Life Time Guarantee
Product Certifications
TOP
FAQ
- What is the best way to utilize Smoke Detector Tester? - Building/facilities/transportation support technicians, home/condo owners and apartment residents should establish routine procedures to inspect, clean, test
and replace batteries in smoke detectors on a quarterly basis. Maintenance and testing should be performed more frequently in areas with large quantities of airborne particulates such as factories or restaurants.
Please Note: If the smoke detectors being tested are part of a centrally monitored alarm system, please notify the
monitoring company PRIOR to testing that a test is scheduled and for what period to prevent the local Fire Department from
being unnecessarily deployed.
TOP
The following products are recommended for use with Smoke Detector Tester.
Also, consider purchasing Smoke Detector Tester by the 288 pack case
(Model #SAT-288) or pallet
(Model #SAT-5760). Buying canned smoke in bulk
is the most cost effective strategy as large quantity discounts apply.
TOP
Uses
Smoke Detector Tester ½ oz size can be used in a variety of ways as shown below:
- Fire Departments can distribute ½ oz sample cans throughout their service areas to promote fire awareness and safety.
- Fire safety professionals can setup demonstrations for proper smoke detector handling in schools and other public events. ½ oz Smoke Check™ is an inexpensive
hand-out.
- HVAC technicians, plumbers, electricians and home inspectors can use ½ oz Smoke Check™ as a leave behind thank you gift to customers..
- Give employees have Smoke Detector Test in their homes.
- ½ oz Smoke Check™ is perfect for home owners and apartment residents to safely verify their smoke detectors are functioning.
- Donate ½ oz Smoke in a Can to schools, hospitals, churches and other not for profit organizations. Use press releases to advertise these good works sponsored by your company.
TOP
Blog
Visit the InspectUSA.com
Blog to learn more about
enhancing workplace and home safety.
Manual
Please follow the instructions shown below for servicing your smoke detector and the proper use of Smoke Detector Tester.
- Clean smoke detector by using DustAir™ Smoke Detector Cleaner or use a clean cloth and gently remove dust and any foreign matter.
- Press test button to verify the battery is operating. Replace smoke detector batteries at least every six months.
- Remove cap and from a distance of between 2' and 4' aim spray for 1 to 2 seconds at the vents or side of the smoke detector.
- Alarm should sound within 1 to 10 seconds if the detector is functioning properly.
- Smoke detectors with delay circuits should be sprayed an additional 1 or 2 times to activate the alarm.
- Remember, as stated above, if the smoke detectors being tested are part of a centrally monitored alarm system, please notify the
monitoring company PRIOR to testing that a test is scheduled and for what period to prevent the local Fire Department from
being unnecessarily deployed.
TOP