| Circuit |
Custom one-chip microprocessor LSI circuit |
| Display |
* LCD Size : 81.4 X 54 mm ( 3.2 X 2.1 inch ) * TFT LCD (320 X 240 pixels ) with back light. |
| Measurement Unit |
* V (phase-to-phase) * V (phase-to-ground) * A (phase-to-ground) * KW / KVA / KVAR / PF (phase) KW / KVA / KVAR / PF (system) KWH / KVAH / KVARH / PFH (system) * Power factor * Phase angle * Frequency * Harmonics display. |
| Over input |
/ |
| Zero |
/ |
| Sampling Time |
Approx. 1 second. |
| Data Hold |
Freeze the display reading. |
| Memory Recall |
/ |
| Altitude (max) |
2000 meters |
| Data output |
RS232 computer serial interface : * Connect the optional USB cable USB-01 will get the USB plug. * Connect the optional RS232 cable UPCB-02 will get the RS232 plug. |
| Operating Temperature |
0 to 50°C ( 32 to 122°F ). |
| Operating Humidity |
Less than 80% R.H.. |
| Power Supply |
* DC 1.5V, AA ( UM-3 ) Battery X 8 PCs (Alkaline or heavy-duty battery). * AC to DC 9V power adapter. |
| Power Consumption |
* Meter : 362 DCmA. * Clamp : 22 DCmA. |
| Weight |
* Meter : 840g ( meter only ) * Clamp ( with cable ) : 500g |
| Dimensions |
Meter : 225 X 125 X 64 mm ( 8.86 X 4.92 X 2.52 inch ) Clamp : 210 X 64 X 33mm ( 8.3 X 2.5 X 1.3 inch ) Clamp Jaw : 86 mm (3.4 inch)- outside |
| Wire connections |
1P/2W, 1P/3W, 3P/3W, 3P/4W. |
| Voltage ranges |
10 ACV to 600 ACV, auto range. |
| Current ranges |
* Current probe input signal volage ( ACV ) : 200mV/300mV/500mV/1V/2V/3V. * Current probe input current range ( ACA ) : 20 A/200A/2000A (1200 A)/30A/300A/3000A 60A/600A/6000A * Meter can cooperate the universal current probe. |
| Safety standard |
IEC1010 CAT III 600 V. |
| ACV input impedance |
10 Mega ohms. |
| Range select |
ACV Auto range. ACA Manual range. |
| Clamp frequency response |
40 Hz to 1 KHz. |
| Spec. tested frequency |
45 to 65 Hz. |
| Over load protection |
ACV :720 ACV rms ACA :1300 ACA with clamp probe * For the Clamp ,CP-1201 |
| Over Indicator |
* LCD display show " OL ". * The data save into the SD card will show " 9999 " or " 999 " ( overleap the decimal point ). |
| Under Indicator |
* The data save into the SD card will show " 9999 " or " 999 " ( overleap the decimal point ). |
| Data Recording |
SD Card |
| Real time data logger |
* Real time data logger, saved the data into SD memory card and down load the all the measured value with the time information ( year/month/data/hour/minute/second ) download to the Excel * Sampling time for data logger : 2 seconds to 7200 seconds, the during of setting step are 2 seconds. |
| Data Output USB/RS232 |
RS232 computer serial interface : * Connect the optional USB cable USB-01 will get the USB plug. * Connect the optional RS232 cable UPCB-02 will get the RS232 plug. |
| Clamp max. conductor Size |
50 mm ( 2.0 inch ) Dia. * For the Clamp ,CP-1201 |
| Rated Tripping Current Settings |
/ |
| Test Current Duration |
/ |
| Operating Factor |
/ |
| Tested Mains Voltage |
/ |
| Standard Accessories |
* Instruction Manual (1 PC) * Test Leads (1 Set, 4 PCs) * Alligator Clips (1 Set, 4 PCs) * Clamp Probes (3 PCs, CP-1201) * AC to DC 9V Adapter (1 PC) * Carrying Case (1 PC) |
| Optional Accessories |
* 2000 Amp current probe, CP-2000 * 200 Amp current probe, CP-200 * 1200 Amp current probe, CP-1201 * Flexible 3000 Amp current probe, CP-3000, CPF-3002,CP-3001, CP-6001 * USB Cable , USB-01 * RS232 cable, UPCB-02 * Data Acquisition software, SW-U811 |